Climate Zones

Changes to the Building Code mean that new houses will typically need to achieve higher R-values for the walls, windows and roofs. Most new houses are currently built to a standard set of R-values, shown in Table 1. These R-values will change as the new insulation requirements take effect.
The new R-values are listed in Table 2. These show the overall R-values for each part of the building, and are different to the R-value of the insulation that is actually installed. For example, a timber-framed wall will need insulation with an R-value of between 2.2 and 2.8 to achieve an overall R-value of 2.0 (the higher insulation R-value offsets the lower R-value of the timber framing).
Insulation values can be found in the BRANZ House Insulation Guide 200
7.

 

  Zone 1 before 30/09/08 Zone 2 before 30/06/08 Zone 3 before 31/10/07
Roof R 1.9 R 1.9 R 2.5
Wall R 1.5 R 1.5 R 1.9
Floor R 1.3 R 1.3 R 1.3
Vertical glazing - - -
Skylights - - -

  Zone 1 after 30/09/08 Zone 2 after 30/06/08 Zone 3 after 31/10/07
Roof R 2.9 R 2.9 R 3.3
Wall R 1.9 R 1.9 R 2.0
Floor R 1.3 R 1.3 R1.3
Vertical glazing R 0.26 R 0.26 R 0.26
Skylights R 0.26 R 0.26 R 0.31
Website by Amplifi Creative